Types of MCB (Miniature Circuit Breaker)
MCB (Miniature Circuit Breaker) is a protective electrical device that automatically disconnects a circuit during overload or short-circuit conditions to protect wiring and equipment.
1️⃣ Types of MCB Based on Tripping Characteristics (Trip Curve)
🔹 Type B MCB
Tripping Current: 3 to 5 times rated current (In)
Best For: Low inrush current l
Types of MCB (Miniature Circuit Breaker)
MCB (Miniature Circuit Breaker) is a protective electrical device that automatically disconnects a circuit during overload or short-circuit conditions to protect wiring and equipment.
1️⃣ Types of MCB Based on Tripping Characteristics (Trip Curve)
🔹 Type B MCB
Tripping Current: 3 to 5 times rated current (In)
Best For: Low inrush current loads
Applications:
Residential lighting
Socket outlets
Example:
10A Type B MCB trips at 30–50A
Common Use: Homes and apartments
🔹 Type C MCB
Tripping Current: 5 to 10 times In
Best For: Medium inrush current
Applications:
Air conditioners
Water pumps
Small motors
Example:
16A Type C MCB trips at 80–160A
Common Use: Commercial buildings
🔹 Type D MCB
Tripping Current: 10 to 20 times In
Best For: High inrush current
Applications:
Heavy motors
Transformers
Welding machines
Example:
32A Type D MCB trips at 320–640A
Common Use: Industrial installations
🔹 Type K MCB
Tripping Current: 8 to 12 times In
Best For: Motor protection
Applications:
Induction motors
Compressors
Example:
20A Type K MCB trips at 160–240A
Special Feature: Handles motor starting current better
🔹 Type Z MCB
Tripping Current: 2 to 3 times In
Best For: Highly sensitive circuits
Applications:
PLC panels
Electronic and control circuits
Example:
6A Type Z MCB trips at 12–18A
Common Use: Control panels
2️⃣ Types of MCB Based on Number of Poles
🔹 SP (Single Pole)
Protects Phase only
Used in single-phase circuits
Example: Lighting circuits
🔹 DP (Double Pole)
Protects Phase + Neutral
Provides complete isolation
Example: Residential main MCB
🔹 TP (Triple Pole)
Protects Three phases
Used in three-phase loads
Example: Motor circuits
🔹 TPN (Triple Pole + Neutral)
Protects 3 Phase + Neutral
Used in distribution boards
Example: Industrial panels
🔹 FP (Four Pole)
Protects All poles including neutral
Used where neutral protection is required
3️⃣ Types of MCB Based on Rated Current
Rated Current /Typical Application
6A Lighting
10A Fans & lights
16A Power sockets
20A Air conditioners
32A Water heaters
40A–63A Main incomer
4️⃣ Types of MCB Based on Breaking Capacity
🔹 6 kA
Domestic use
Homes & apartments
🔹 10 kA
Commercial buildings
Offices, malls
🔹 16 kA
Industrial use
Factories
5️⃣ Practical Examples
🏠 Residential Installation
Lighting circuit → 6A Type B
Socket circuit → 16A Type B
AC circuit → 20A Type C
Main incomer → 40A DP MCB
🏭 Industrial Panel
Motor protection → 32A Type D
Control circuit → 6A Type Z
Incomer → 63A TPN MCB
🔑 Summary
MCB Type/Trip Range/Typical Use
B 3–5 × In Residential
C 5–10 × In Commercial
D 10–20 × In Industrial
K 8–12 × In Motors
Z 2–3 × In Electronics